1. 3M Products
  • 3M™ Cold Shrink QT-II Three Core Cable Termination 92-EB63-3. 3 terminations/kit
  • 3M™ Cold Shrink QT-II Three Core Cable Termination 92-EB63-3. 3 terminations/kit

    3M ID 7000035265
    • Designed for 12 kV Umax voltage class, three-core, polymeric power cable systems
    • Suitable for copper wire or tape screened cables, with or without armour
    • Indoor application range 120-150 mm²
    • Fast and easy installation at temperatures ranging from -20 °C to +50 °C
     More...
    Product Details
    • Designed for 12 kV Umax voltage class, three-core, polymeric power cable systems
    • Suitable for copper wire or tape screened cables, with or without armour
    • Indoor application range 120-150 mm²
    • Fast and easy installation at temperatures ranging from -20 °C to +50 °C
    • No heat/flame or tools are required for installation

    3M™ Cold Shrink Termination QTII 92-EB63-3 is our kit containing 3M™ Cold Shrink QTII silicone termination body with integrated stress control device, silicone elastomeric insulation, armour continuity components, rejacketing tubes, three-core Cold Shrink breakout boots, silicone tape and detailed instructions for installing.

    For 12 kV Umax voltage class, three-core, polymeric power cable systems, use 3M™ Cold Shrink Termination QTII 92-EB63-3. Our termination kit is designed for power cables with copper wire, tape screen or armour according to HD 620 (IEC 60502), and has a 120-150 mm² indoor application range. It features a prefabricated Cold Shrink termination body which allows fast and easy installation on a wide range of cable types and sizes, at temperatures ranging from -20 °C to +50 °C. The constant force springs offer a solderless earth connection and includes silicone tape for moisture sealing. No heat/flame or tools are required for Cold Shrink installation. 3M™ Cold Shrink Termination QTII 92-EB63-3 meets and exceeds the requirements of European Standard CENELEC HD 629.1 and IEC 60502-4.

    Specifications
    Applications
    Cable Termination
    Cable Insulation Outside Diameter Range (metric)
    19,8 - 33,0 mm
    Cable Type
    Polymeric insulated, copper screened, armored/unarmored cable
    Conductor Size Range
    120 - 150 mm²
    Indoor/Outdoor
    Indoor
    Lug/Stem Connector Included in Kit
    No
    Maximum Wire Gauge
    150mm²
    Minimum Wire Gauge
    120mm²
    Number of Conductors
    3
    Number of Skirts
    0
    Product Type
    Cold shrinking
    Voltage Application
    Medium Voltage
    Voltage Rating
    6/10 KV
    Follow Us
    The brands listed above are trademarks of 3M.
    Change Location
    United Kingdom - English